Products

Our MCB breaking capacity is up to 10-15KA , the DC

voltage for MCB MCCB SPD is up to 1500V.

HS2X-RJ45 Data and Signal Surge Protection

Application

Ethernet networks
Security systems
IT / Data centers
Data communications
Highly exposed Ethernet
Surveillance cameras
Industrial automation
Features/Benefifits

Easy installation

Fail-safe /self-protected design

Very fast response

Hybrid GDT and Diode Technology

10/100/1000 Mbps and Gigabit Compatible

High-Speed Protector technology

Bi-Directional Protection

Shielded Enclosure and Connectors

Plug-in format

HS2X-RJ45 is the series of devices for discharging transient overvoltages induced in Ethernet Category 5.E and 6 networks.In accordance with IEC 61643-21. In-line format.

■Suitable for the protection of communications equipment connected to Ethernet networks. By their nature, they are highly exposed to induced transient overvoltages (surges) associatedwith meteorological activity.

■No installation required. It connects directly to the equipment to be protected via RJ45 connectors.

■Input/Output connectors: RJ45 (female).

■Available with optional Din-rail mountable.

Dimensions
Data sheet
Type

Technical Data Application

 

HS2X-RJ45-6

 

HS2X-RJ45-24

 

HS2X-RJ45-POE

 

HS2X-RJ45- CAT6-1000

 

HS2X-RJ45-CAT6-POE

Cat 5 , Cat 5e

Cat 6

Maximum Data Rate100Mbit/s1000Mbit/s
Bandwidth100MHz250MHz
Nominal voltage (Un)

5Vdc

24Vdc

48Vdc

5Vdc

48Vdc

Maximum continuous operating voltage (UC)

6Vdc

30Vdc

65Vdc

6Vdc

65Vdc

Voltage protection level (8/20μs) (Up)

≤ 30V

≤ 40V

≤ 100V

≤ 30V

≤ 100V

Nominal discharge current (8/20μs) (In)

3kA

Maximumworking current (IL)

300mA

Series resistance (RS)

15Ω

Response time (tA)

< 10ns

Degree of protection

IP 20

Pins Protected

1,2,3,6

1-2,3-6,4-5,7-8

External materials

Aluminum

Temperature range

-40ºC~+80ºC

Altitude

13123 ft [4000m]

Connection (input – output)

RJ45

Type of connectionSeries (two ports)
For mounting onOptional Din-rail mountable
Place of installationindoor installation
Type of SPD

C2,C3

Product standards

IEC 61643-21, EN 61643-21

×
Please use this form to order our products
good service
Blank Form (#3)