Products

Our MCB breaking capacity is up to 10-15KA , the DC

voltage for MCB MCCB SPD is up to 1500V.

HO231N-40 Residual Current Circuit Breaker With Over-Current Protection (RCBO)

The new RCBO is a single pole plus switched neutral device where the line/load can be connected from top or bottom. Having no restriction to the connection of supply enhances the safety of your installation and the compact.Single pole size allows more poles to fit into assemblies offering a cost effective solution.

Fully conforms to AS/NZS 61009-1
Compliant to Energy Safe Victoria – Additional Testing Requirements for RCBOs
Rated current up to 40A
Type AC and Type A sensitivity devices available

It achieved Australia SAA certificate ,and pass the ESV test ,It is can be wired in either direction

 

Technical Data
Electrical
Design according toIEC61009-1 AS/NZS61009-1
Number of poles1P+N
Active and neutral poles switched
Rated current In:6 – 40A
Rated voltage Un230/240 Vac
Rated frequency50/60 Hz
Voltage range for protective function50 – 253V
Rated short circuit capacity4.5kA
Rated residual making/breaking capacity3kA
Tripping characteristicB,C
Rated tripping current IΔn250A (8/20us)
Rated tripping current IΔno10, 30mA
Residual current sensitivityAC, A
Rated non-tripping current IΔno0.5 IΔno
Rated Insulation voltage500V
Dielectric strength2.5kV
Selectivity class3
Operating temperature-5 to 40ºC
EnduranceElectrical comp. >10,000 operating cyclesMechanical comp. >30,000 operating cycles
Mounting3-Position DIN rail clip, permits removal from existing busbar system
Load terminalsLoad terminalsOpen mouthed/lift terminals
Line terminalsOpen mouthed/lift terminals
Terminal protectionFinger and hand touch safe
Terminal capacity1 – 16 mm2
Terminal screw torque1.2Nm
Degree of protection, switchIP20
Degree of protection, built-inIP40
Resistance to climatic conditionsacc. To IEC/EN 61009
Dimensions(mm)
×
Please use this form to order our products
good service
Blank Form (#3)