We are also specializing in improving the things management and QC method in order that we could retain terrific edge inside the fiercely-competitive small business for Led Street Light Spd, 400vdc Spd, Spd 2p 40ka 800v, Welcome to post your sample and color ring to let us produce according to your specification.Welcome your inquiry! Looking forward to building long-term cooperation with you!
Factory Cheap Hot Spd Breakers - HS2W series Data and Signal Surge Protection – HONI electric Detail:
Features/Benefifits
Easy installation
Low Insertion Loss
Wide operating frequency spectrum
Very fast response
High Energy GDT Technology
Field Replaceable GDT
Waterproof Design
DC Pass confifiguration
Bi-Directional Protection
Good transmission effect
Strong anti-interference
complies IEC 61643-21 standard
SPD for Coaxial & Radio frecuency (RF) Systems
HS2W is the series of devices for discharging transient overvoltages induced in coaxial lines. In accordance with IEC 61643-21. Coaxial format.
■Suitable for the protection of radiofrequency transmission and reception equipment.
By their nature, they are highly exposed to induced transient overvoltages (surges) associated with meteorological activity.
■For BNC, F, N, TNC,connectors.
■Ideal for the protection of transmission and reception systems such as TV and radio antennas, closed circuit TV (CCTV), alarms, etc.
■Discharge capacity with an 8/20 μs waveform: 20 kA.
Data sheet
Type
Technical Data
Frequency |
HS2W-BNC,HS2W-F,HS2W-N,HS2W-TNC 0-3GHZ
|
Maximum continuous operating voltage (UC) |
230V
|
Nominal discharge current (8/20μs) (In) |
10kA
|
Maximum discharge current (8/20μs) (Imax) |
20kA
|
Voltage protection level (8/20μs) (Up) |
≤ 600V
|
Maximum Current |
10A
|
Maximum peak power |
100W
|
Impedance |
50Ω
|
Insertion Loss |
< 0.2dB
|
Return Loss |
> 20dB
|
VSWR |
< 1.2:1
|
Response time (tA) |
< 100ns
|
Degree of protection |
IP 65
|
Enclosure Material |
Metal
|
Temperature range |
-40ºC~+80ºC
|
Altitude |
13123 ft [4000m]
|
Connection |
BNC, F, N ,TNC
|
Housing |
In-line Installation
|
Field Replaceable GDT |
YES
|
Type of SPD |
C2,C3
|
Product standards |
IEC 61643-21, EN 61643-21
|
Dimensions
Product detail pictures:
Related Product Guide:
Our advancement depends on the superior gear ,superb talents and consistently strengthened technology forces for Factory Cheap Hot Spd Breakers - HS2W series Data and Signal Surge Protection – HONI electric , The product will supply to all over the world, such as: Manila, Marseille, Mecca, Our company follows laws and international practice. We promise to be responsible for friends, customers and all partners. We would like to establish a long-term relationship and friendship with every customer from all over the world on the basis of mutual benefits. We warmly welcome all old and new customers to visit our company to negotiate business.