Looking for Exclusive Agency and Distributor! Welcome Contact:0086-18966276297 0086-577-61718910
Technical Data |
|||||||||
|
IS-16 |
IS-20 |
IS-25 |
IS-32 |
IS-40 |
IS-63 |
IS-80 |
IS-100 |
IS-125 |
Electrical |
|||||||||
Design |
according to IEC/EN 60947-3 |
||||||||
Rated voltage |
240/415 V |
||||||||
Frequency |
50/60 Hz |
||||||||
Rated insulation voltage Ui |
690 V~ |
|
|
|
|
|
|
|
|
Rated imdpulsle withstand voltage Uimp |
6 kV |
||||||||
Pollution degree |
3 |
||||||||
Technical Data |
|||||||||
Rated short-time withstand current Icw |
2 kA |
||||||||
Rated short-circuit making capacity Icm |
2.8 kA |
||||||||
Rated current 240/415V, AC23A |
16A |
20A |
25A |
32A |
40A |
63 |
80 |
100 |
125 |
Number of poles |
1-, 2-, 3-, 4-poles |
||||||||
Maximum back-up fuse |
125 A gG |
|
|
|
|
|
|
|
|
Shorat circruiit strtength - with back-up fuse according to IEC/EN 60947-3 |
12.5 kA |
12.5 kA |
12.5 kA |
12.5 kA |
12.5 kA |
12.5 kA |
12.5 kA |
10kA |
10kA |
Endurance |
|||||||||
Electrical components operation cycles |
≤ 3000 |
≤ 3000 |
≤ 3000 |
≤ 3000 |
≤ 3000 |
≤ 3000 |
≤ 3000 |
≤ 3000 |
≤ 2000 |
Mechanical components operation cycles |
≤ 16000 |
≤ 16000 |
≤ 16000 |
≤ 16000 |
≤ 16000 |
≤ 16000 |
≤ 16000 |
≤ 16000 |
≤ 14000 |
Mechanical |
|||||||||
Frame size |
45 mm |
||||||||
Device height |
80 mm |
||||||||
Device width |
17.5 mm/Pol |
||||||||
Mounting |
quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 |
||||||||
Degree of protection, built-in |
IP40 |
||||||||
Terminal protection |
finger and hand touch safe according to BGV A3 |
||||||||
Terminals top and bottom |
open mouthed/lift terminals |
||||||||
Terminal capacity |
2.5 - 50 mm² |
||||||||
Busbar thickness |
0.8 - 2 mm |
||||||||
Fastening torque of terminal screws |
2.5 - 5 Nm |
||||||||
Function |
irrespective of the position of installation |