Products

Our MCB breaking capacity is up to 10-15KA , the DC

voltage for MCB MCCB SPD is up to 1500V.

❮
❯

HS2XJ Data and Signal Surge Protection

Application

DC distribution
Industrial automation
Telecommunications
Motor controls systems
PLC applications
Power transfer equipment
DC drives
UPS systems
Security systems
IT / Data centers
Medical equipment
Features/Benefifits

Easy installation

Fail-safe /self-protected design

Very fast response.

Hybrid GDT and Diode Technology

Connection with screw pressure.

Allows the connection of lines with a very small size.

Plug-in format

HS2XJ is the series of devices for discharging transient overvoltages induced in RS 485 networks.OBVXJ designed for protection of data, communication, mea-suring and control lines against surge effects.The protector with RS485 input and output connectors, able to hold up nominal discharge currents of 5kA for each line.

■Suitable for the protection of instrumentation installed in RS 485 networks. By their nature, they are highly exposed to induced transient overvoltages (surges) associated with meteorological activity.

■Protection of 1 or 2pairs of wires.

■For nominal voltage. Un : 12V,24V,48V.

■Low residual voltage in all the working voltages.

■Available with optional Din-rail mountable.

Dimensions
Data sheet
TypeTechnical Data ApplicationHS2J-2 / HS2J-4control line
Product standardsIEC 61643-21, EN 61643-21
Type of SPDC3
Nominal voltage (Un)6Vdc / 12Vdc / 24Vdc / 48Vdc
Maximum continuous operating voltage (UC)8Vdc / 15Vdc / 30Vdc / 65Vdc
Nominal discharge current (8/20μs) (In)5kA
Maximum discharge current (8/20μs) (Imax)10kA
Voltage protection level (8/20μs) (Up)≤12V/ 25V/ 40V/ 75V
Maximumworking current (IL)300mA
Series resistance (RS)15Ω
Response time (tA)< 10ns
Degree of protectionIP 20
Lines Protected1 or 2pairs
External materialsAluminum
Temperature range-40ºC~+80ºC
Altitude13123 ft [4000m]
Connection (input – output)terminals
Conductor Cross Section (max)4mm2 (Solid) / 2.5mm2 (Flexible)
Terminal Screw Torque0.5Nm
For mounting onOptional Din-rail mountable
Place of installationindoor installation
×
Please use this form to order our products